Output voltage regulation: BATTERY MODE - PWM sine wave 120V +/-5%
Output frequency regulation: LINE MODE - Passes line frequency of 60Hz +/-10%; BATTERY MODE - Inverter output regulated to 60Hz +/-0.5Hz
Outlet quantity / type: 6x NEMA 5-15R
Input:
Maximum input amps: 10A / 1200 watts
Input connection type: NEMA 5-15P
Input cord length: 6 ft., 16 gauge
Recommended electrical service: 15A 120V
Battery:
Full load runtime: 5 minutes (550VA)
Half load runtime: 17 minutes (275VA)
DC system voltage: 12 V DC
Typical battery lifespan: 3~6 years, depending on usage
Battery recharge rate: 2~4 hours to 90%
Replacement Battery Cartridge: RBC51
Voltage Regulation:
Direct pass through: Voltages of 106V and greater are passed through to connected equipment unchanged
Brownout correction: Input voltages between 83 and 105 are boosted by 14%
LEDs Alarms & Switches:
Front panel LEDs: 4x LEDs indicate performance conditions
Alarms: Audible alarm with 15 second delay sounds to indicate loss of utility power. Alarm can be silenced by pressing front panel alarm cancel button. Once silenced, alarm will re-sound when approximately 2 minutes runtime remain.
Switches: Includes 2x front panel switches
Surge / Noise Suppression:
AC surge suppression: 480 joules
AC suppression response time: Instantaneous
Dataline suppression: Tel/DSL
EMI / RFI AC noise suppression: Yes
Communications:
Network monitoring port: USB
Software and cabling included: USB cabling included, PowerAlert software available for free download
WatchDog compatibility: Yes, compatible with Tripp Lite´s Watchdog system service to restore operation to locked equipment through soft reboot of application / OS or hard power off/on reboot of connected equipment - ideal for unattended kiosk applications
Line / Battery Transfer:
Transfer time from line power to battery mode: 2~4 milliseconds
Low voltage transfer to battery power: Switches to battery power as line voltage decreases to 83 volts or less. Resets to line power mode as line voltage increases to 87V or higher
High voltage transfer to battery power: Switches to battery power as line voltage increases to 147 volts or higher. Resets to line power mode as line voltage decreases to 143V or less
Special Features:
Cold Start: Yes, inverter can be "cold started" to enable temporary AC output during a power failure
Appearance: Attractive all-black tower UPS
Certifications: UL1778 (USA), cUL (Canada), FCC Class B (emissions), NOM (Mexico), FCC Part 68 / Industry Canada (Telecommunications)
Material of construction: PVC
Form factors supported: Tower
Cooling method: Convection
Battery Access: Battery access door allows user replacement of UPS batteries
Dimensions (WxDxH): 5 x 6.5 x 8.5 inch / 12.7 x 16.5 x 21.6 cm
Weight: 14.4 lbs. / 6.5 kg
Why can't I see the price?
This display appears for low price items and indicates that additional discount is applicable on adding the item to the Shopping Cart. You can view the discounted price by selecting the item and then adding the item to cart. Adding the item to cart does not imply that you are obliged to buy it – you can always delete the item from your cart if you decide not to buy it.